Heat Exchanger LMTD Calculator

Counterflow terminal approaches are hot-in minus cold-out and hot-out minus cold-in.

200 / HEAT EXCHANGER LMTD

Your numbers.
A clearer decision.

Free to use. No signup.
Inputs stay in this browser.

Starting values are illustrative. Use your own costs, rates and assumptions.

INPUT GROUP 01

Entered quantities and model assumptions

Illustrative defaults are examples. Replace them with matching measurements, reviewed properties and actual quote terms.

YOUR CALCULATION

Calculate the ideal two-terminal log mean temperature difference.

First terminal approach · K

60

Second terminal approach · K

40

Log mean temperature difference · K

49.326

Keep the calculation

Saving is optional and stays on this device. Unsaved edits are not kept when you leave. CSV includes every input and the current results.

Illustrative inputs loaded. Replace them with your own assumptions.

How the heat exchanger lmtd calculator works

Counterflow terminal approaches are hot-in minus cold-out and hot-out minus cold-in. Co-current approaches are hot-in minus cold-in and hot-out minus cold-out. LMTD = (larger approach − smaller approach) ÷ ln(larger/smaller). Equal approaches return their common value; log1p is used for nearby values.

Both terminal approaches must be positive. Hot inlet must not be colder than hot outlet, and cold outlet must not be colder than cold inlet in this model. Counterflow cold outlet may exceed hot outlet if both approaches remain positive. No multipass correction, flow balance, exchanger sizing or mechanical suitability is inferred.

Quantities use the stated units and finite bounded inputs. Whole purchases round up under the documented model; cost components round half-up to cents before totals are summed. Undefined ratios stay unavailable. π and logarithms use normal numeric precision. Display rounding does not alter the entered assumptions.

Worked example

Counterflow temperatures 100→60°C hot and 20→40°C cold give 60 K and 40 K approaches. LMTD is 20/ln(1.5), about 49.326 K. Changing hot outlet to 80°C makes both approaches 60 K, so LMTD is exactly 60 K.