Storage & energy planning

Battery Runtime Scenario Calculator

Apply usable share and one-way conversion efficiency to nominal DC energy, then divide available AC energy by a constant AC load.

111 / ESTIMATE CONSTANT-LOAD DURATION

Your numbers.
A clearer decision.

Free to use. No signup.
Inputs stay in this browser.

Starting values are illustrative. Use your own costs, rates and assumptions.

INPUT GROUP 01

Nominal DC energy boundary

INPUT GROUP 02

Constant AC-side loads

YOUR CALCULATION

Estimate constant-load duration from an entered DC energy boundary.

Available DC energy after usable-share assumption · kWh

8

AC energy after discharge conversion · kWh

7.2

Combined constant AC load · kW

1.3

Ideal constant-load runtime · h

5.538

Keep the calculation

Saving is optional and stays on this device. Unsaved edits are not kept when you leave. CSV includes every input and the current results.

Illustrative inputs loaded. Replace them with your own assumptions.

How the battery runtime scenario calculator works

Available DC energy = nominal DC kWh × usable share / 100. Available AC energy = that DC energy × one-way discharge efficiency / 100. Each factor applies once. Manufacturer capacities may already use a usable or AC boundary; do not reapply these factors to such a value without reconciling the basis.

Combined constant AC load is main load plus AC-side auxiliary load. Ideal runtime hours = available AC kWh ÷ combined kW. Zero combined load makes runtime unavailable, rather than displaying an infinite duration. Zero available energy with positive load gives zero modeled runtime.

Energy and power limits are separate. This arithmetic does not certify continuous or surge power, inverter capability, current, wiring, safety or emergency-backup performance. Temperature, aging, voltage-dependent capacity, variable loads and self-discharge are excluded. Tesla’s specification illustrates the distinction between usable energy and output power; none of its product ratings are used as the defaults.

Worked example

10 kWh nominal DC at 80% usable share gives 8 kWh available DC. At 90% one-way discharge efficiency, 7.2 kWh is available on the AC side. A 1.2 kW main load plus 0.1 kW auxiliary load gives about 5.538 hours ideal runtime. Increasing main load to 1.7 kW gives exactly four hours under the same energy assumptions.

Sources and assumptions

The source material explains the underlying calculation or pricing structure. Entered prices, costs, schedules and scenario choices are your assumptions; this tool does not obtain supplier quotes or predict actual results.

Calculation methods, testing and sources · Practical calculation guides